text.skipToContent text.skipToNavigation

U2GT003 Distance Sensor

Available from stock
These ultrasonic sensors evaluate the sound reflected from the object. They can detect almost any object and are especially well suited for monitoring fill levels of liquids and bulk goods and for detecting transparent objects regardless of the material, state, color or transparency. The measured value can be read out via IO-Link, and the sensor can be optimally adapted to the application. The stainless steel housing in hygienic design enables use in demanding environments such as washdown and hygienic areas. The sensor can be used both in reflex mode operation, and as an ultrasonic through-beam sensor.

Ultrasonic Data

Working range, reflex sensor 50 ... 600 mm
Working range, through-beam sensor 50 ... 1,200 mm
Setting Range 50 ... 600 mm
Reproducibility maximum 4 mm
Linearity Deviation 4 mm
Resolution 1 mm
Ultrasonic Frequency 260 kHz
Opening Angle < 13 °
Service Life (T = +25 °C) 100,000 h
Switching Hysteresis 2 % *

Electrical Data

Supply Voltage 18 ... 30 V DC
Current Consumption (Ub = 24 V) < 35 mA
Switching frequency, reflex sensor 10 Hz
Switching frequency, through-beam sensor 10 Hz
Response time, reflex sensor 50 ms
Response time, through-beam sensor 50 ms
Temperature Drift < 10 %
Temperature Range -30 ... 60 °C
Number of Switching Outputs 1
Switching Output Voltage Drop < 2.5 V
Switching Output/Switching Current 100 mA
Analog Output 4...20 mA
Short Circuit Protection yes
Reverse Polarity Protection yes
Overload Protection yes
Interface IO-Link V1.1 Smart Sensor Profile
Data Storage yes
Protection Class III

Mechanical Data

Setting Method IO-Link
Teach-In
Housing Material Stainless steel, V4A (1.4404 / 316L)
Sensing face Stainless steel, V4A
Degree of Protection IP68/IP69K
Connection M12 × 1; 4/5-pin
Ecolab yes
Weight 65 g

Safety-relevant Data

MTTFd (EN ISO 13849-1) 1,192.59 a

Output

Error Output yes
Analog Output yes
IO-Link yes

Adjustable parameters

Analog output 4...20 mA
0...10 V
Output NPN
PNP
Error Output
Circuit NC
NC/NO
NO
Other parameters Filter
Unit of measure
Adjustable sonic cone
Through-beam mode
Teach-in mode
All other parameters can be found in the product documentation.

Standards and certificates

B_SYM_RoHS_01.pdf B_SYM_RoHS_01.pdf B_SYM_RoHS_01.pdf B_SYM_RoHS_01.pdf B_SYM_RoHS_01.pdf B_SYM_RoHS_01.pdf B_SYM_RoHS_01.pdf
* Referring to the switching distance, at least 2 mm.

Connection Diagram

Characteristic response curve

Characteristic curves show the position of the center or the front edge of the measured object (100 × 100 mm plate) at the time of switching.
Ob = Object
Sc = Sonic cone width
Standard sonic cone (center of the measured object)
Extra-narrow sonic cone (center of the measured object)
Standard sonic cone (front edge of the measured object)
Characteristic response curve
Characteristic curves show the position of the center or the front edge of the measured object (Ø 25 mm rod) at the time of switching.
Ob = Object
Sc = Sonic cone width
Standard sonic cone (center of the measured object)
Extra-narrow sonic cone (center of the measured object)

Dimensioned Picture

Dimensions specified in mm (1 mm = 0.03937")
1 = Sensing Face

Complementary Products

  • IO-Link Master
  • Software
Initial start-up instructions
Operating instructions
System solution
Product description file
Product description file
wenglor-U2GT003-20230724-IODD1.1.zip
Interface protocol
Interface protocol
Interface_Protocol_IO-Link_Parameter_Process_Data_U2GT003_U2GT004.pdf
Declarations of Conformity / Approvals
Product certificates
Product certificates
U2GT001_002_003_004_FDA_Conformity.pdf U2GTxxx__U2GTxxxSxx_Ecolab.pdf